Flameproof Temperature and Humidity Transmitter – Duct Mount – HTX-440-FLP-DM
HTX-440-FLP-DM – Flameproof Temperature and Humidity Transmitter – Duct Mount.
Technical Specifications :
Item | T + RH sensor cum Transmitter / RH sensor cum Transmitter in FLP head or FLP junction box |
---|---|
Built in Sensors | For Temp.: Pt-100 Class A element (Hayashi-Denko Japan make) |
For %Rh: Capacitive type Humidity sensor (Honeywell USA make) | |
Temp. Range | 0 to 60oC (Std. range for HVAC applications) |
Temp. Output | (0-1) VDC / (4-20) mA / (0-10) VDC proportional to 0 to 60oC or proportional to selected temperature range. |
RLmax = 400 Ohms for 4-20mA, RLmin = 100K for 0-10VDC | |
Temp. Accuracy | ± 0.5 oC |
RH Range | 0 to 100% |
%RH Output | (0-1)VDC / (4-20) mA / (0-10)VDC proportional to 0 to 100%Rh |
RLmax = 500 Ohms for (4-20)mA, RLmin = 100K for (0-10)VDC | |
RH Accuracy | +/- 2% @ 25oC and 50% Rh |
Isolation Voltage | Greater than 1.5KV (4-20mA/0-10VDC Output and 24VDC Supply voltage are electrically isolated) |
Supply Voltage | 24 VDC +/-10% @ 100mA max. |
Type | Duct mounted in the Duct hole of 22 mm. |
Enclosure / SS Stem Size | FLP head or JB as per standard / 20mm Dia.x200mm (std. length) |
Optional : Required non std. stem length can be provided on request. | |
Process Connection | ½ inch BSP Thread below the head |
Cable | 4 core or 6 core PVC/PVC insulated 2meter long with standard colour code. Extra length of cable can be provided against order. |
Precautions for use | Avoid condensation and drench. Avoid exposure to saline, inorganic and organic gas. |