Features : |
|
- Industrial grade design
- Input from HYGROCLIP CP sensor.
- 4-20mA proportional to T and RH.
- IP 65 ABS plastic enclosure.
- Operates on 18 to 36VDC.
|
|
Description : |
|
Libratherm offers T + RH sensor with Transmitter model HYGROTX-3000 and HYGROTX-290 for measuring and transmitting the analogue values proportional to both T and RH Input. The signal generated by Hygroclip is of the order of 1 volt DC and cannot be transmitted over very long distance and if done so the signal is likely to drop over very long cable which will result in the inaccurate measurement of temperature and %RH. The transmitter featured here converts the low level signal to equivalent 4-20mA, which can be transmitted over a long distance without loss of accuracy in the measurement. Dual output of 4-20mA proportional to T and %RH can be used for remote measurement and indication.
To suit industrial requirement more advanced transmitters model HTX-3000 are also available with local display. To facilitate interface with PLC or DCS or with any other process controller – digital serial communication on RS485 bus with MODBUS RTU protocol in slave mode is also provided.
|
|
Technical specifications : |
|
Model |
HYGROTX-3000 |
Sensor Make |
Hygroclip CP – Rotronic Swiss make |
Sensor Cable |
1 meter long |
Sensor Dimension |
L = 140 mm. & D = 15 mm. |
Temp. Range |
-40 to 60 o C |
Temp. O/P |
4 – 20 mA proportional to -40 to 60 oC or 0 to 60 oC.
( Any one - As per user’s requirement) |
Temp. Accuracy |
+/- 0.3 o C |
%RH Range |
0 to 100% |
%RH O/P |
4 – 20 mA proportional to 0 to 100%Rh. |
%Rh Accuracy |
+/- 1.5% |
Loop Resistance |
RLmax = 400 Ohms @ 24VDC |
Supply Voltage |
12 - 36VDC @ 50mA |
Enclosure |
ABS plastic IP-65 with suitable wall mounting clamps. |
Enclosure Size |
85 x 80 x 55 mm. |
|
|
Technical Specification (HYGROTX-290) : |
|
Model |
HYGROTX-290 |
Sensor Make |
H290 – Rotronic Swiss make |
Sensor Cable |
1 meter long |
Sensor Dimension |
L = 200 mm. & D = 15 mm. |
Temp. Range |
-40 to 200 o C |
Temp. O/P |
4 – 20 mA proportional to -40 to 150oC or 0 to 150oC.
( Any one - As per user’s requirement) |
Temp. Accuracy |
+/- 0.3 o C |
%RH Range |
0 to 100% |
%RH O/P |
4 – 20 mA proportional to 0 to 100%Rh. |
%Rh Accuracy |
+/- 1% |
Loop Resistance |
RLmax = 400 Ohms @ 24VDC |
Supply Voltage |
12 - 36VDC @ 50mA |
Enclosure |
ABS plastic IP-65 with suitable wall mounting clamps. |
Enclosure Size |
120 x 80 x 55 mm. |
|